Saint Petersburg
Head office and production site
TU 27.33.13-031-72453807-2017
1Ex db IIC Gb
1Ex eb IIC Gb
Ex tb IIIC Db
РВ Ex db I Mb
РВ Ex eb I Mc

| Cable entry size | Thread, |
Overall dimensions, mm | Weight, kg | D, mm | Ød, mm | Number of wires passed through the cable entry (calculated based on the outlet opening Ød). Cross-section of the wire, mm2 | |||||||||||||||||
| The main thing | Duplicate | AC1 | AC2 | ØM | L | 1 | 1,5 | 2,5 | 4 | 6 | 10 | 16 | 25 | 35 | 50 | 70 | 95 | 120 | 150 | ||||
| KNVS1M | FEC1I/CP | M20 x 1.5 | 26 | 26 | 28,5 | 60 | 0,11 | 13 | 10 | 13 | 8 | 6 | 5 | 4 | 2 | 1 | - | - | - | - | - | - | - |
| KNVS2M | FEC2I/CP | M25 x 1.5 | 34 | 34 | 38 | 64 | 0,20 | 18 | 15 | 31 | 20 | 14 | 11 | 9 | 5 | 3 | 1 | 1 | 1 | - | - | - | - |
| KNVS3M | FEC3I/CP | M32 x 1.5 | 40 | 40 | 44,5 | 74 | 0,24 | 24 | 23 | 73 | 47 | 34 | 26 | 22 | 11 | 8 | 4 | 4 | 2 | 1 | 1 | - | - |
| KNVS4M | FEC4I/CP | M40 x 1.5 | 50 | 50 | 56 | 72 | 0,40 | 30 | 26,5 | 97 | 62 | 45 | 35 | 30 | 15 | 11 | 5 | 5 | 3 | 2 | 1 | 1 | 1 |
| Cable entry size | Thread, NPT | Overall dimensions, mm | Weight, kg | ØD, mm | Ød, mm | Number of wires passed through the cable entry (calculated based on the outlet opening Ød). Cross-section of the wire, mm2 | |||||||||||||||||
| The main thing | Duplicate | AC1 | AC2 | ØM | L | 1 | 1,5 | 2,5 | 4 | 6 | 10 | 16 | 25 | 35 | 50 | 70 | 95 | 120 | 150 | ||||
| KNVS1N | FEC1N/CP | 1/2" | 26 | 26 | 28,5 | 60 | 0,11 | 13 | 10 | 13 | 8 | 6 | 5 | 4 | 2 | 1 | - | - | - | - | - | - | - |
| KNVS2N | FEC2N/CP | 3/4" | 34 | 34 | 38 | 64 | 0,20 | 18 | 15 | 31 | 20 | 14 | 11 | 9 | 5 | 3 | 1 | 1 | 1 | - | - | - | - |
| KNVS3N | FEC3N/CP | 1" | 40 | 40 | 44,5 | 74 | 0,24 | 24 | 23 | 73 | 47 | 34 | 26 | 22 | 11 | 8 | 4 | 4 | 2 | 1 | 1 | - | - |
| KNVS4N | FEC4N/CP | 1 1/4" | 50 | 50 | 56 | 72 | 0,40 | 30 | 26,5 | 97 | 62 | 45 | 35 | 30 | 15 | 11 | 5 | 5 | 3 | 2 | 1 | 1 | 1 |
The maximum permissible number of wires, depending on the core cross-section, for sealing in a bushing.
The specified values correspond to clause 2.1.2, Appendix "C", GOST IEC 60079-1-2011.
An explosion-proof bushing for sealing with compound allows the cable entry to be used for inserting unarmored cables of non-circular cross-sections or those with a structure where the wires do not fit tightly.
The grommet consists of two components: a sleeve and a release element. A two-component epoxy compound, included in the package, is used as a sealant. The main advantage of using this compound, as opposed to liquid compound, is its flexibility, which facilitates cable installation in the gland. In addition to its flexibility, the epoxy compound ensures high bond strength, does not shrink, and is resistant to water, oils, and solvents.
Explosion-proof KNVS cable glands are designed to relieve cable strain. These cable glands provide protection against pull-out without damaging the cable sheath or conductors, and prevent them from being pinched.
Drag files here
CAD " GORELTEX ", questionnaires, necessary documents
Example: KNVS1MNK -TU 27.33.13-031-72453807-2017
- Cable type: unarmored
- Thread: M20x15, metric ISO965
- Material: nickel-plated brass
Head office and production site
Sales office
Sales office
Sales office and production site
Sales office
Sales office