The programmable thermostat GTG-PT is used to maintain specified temperature conditions and control external electrical devices and mechanisms in hazardous areas.
When overheating or overcooling is detected, the GTG-PT can initiate a protective shutdown of the power supply circuits and also signal a violation or malfunction using connected visual signaling devices.
The GTG-PT is available in two models: with a display (GTG-PT/M3) and with LED indication (GTG-PT2/M3). Each model offers two temperature sensor options: a remote sensor on a cable up to 30 m long or a built-in sensor (option /VD).
Advantages
Setting the operating temperature in the range from -55°C to +125°C;
Temperature measurement accuracy from 0.5°C;
Control of up to four external devices simultaneously;
Possibility of placing the sensor at a distance of up to 30 meters from the device body;
Small dimensions of the sensor, easy installation;
Monitoring the status and presence of errors of the temperature sensor, switching to emergency mode in the absence of a signal;
Possibility of replacing the sensor without replacing the device;
The presence of two electrically independent changeover contacts.
1Ex db eb ib IIC T6...T5 Gb Ex ib tb IIIC T85°С...T100°C Db
Marking of mining equipment
RP Ex db eb ib I Mc
РН1/РН2
Degree of protection
IP66
IK10
Installation
Category II for gas subgroup IIA, IIB, IIC, zones 1, 2;
Underground workings that are not hazardous for gas (methane) and coal dust
Technical data
Ambient temperature, °C
-60...+40 (T6/T85°C) -60...+60 (T5/T100°C) -60...+60 (for normal mine and general industrial designs) -55...+125 (range of temperature measured by the sensor)
Switching voltage, V
~270 (400 max.) / ⎓270
Operating voltage range, V
~110…270 ⎓110…270
Maximum switching current
2 channels of 16A
Current consumption, A
0.09…0.06 (AC) 0.05…0.02 (DC)
Maximum power consumption, W
5
Enclosure material
Impact-resistant, fiberglass-reinforced polyamide with antistatic modifiers
Temperature measurement range, °C
-55...+125
Accuracy of measured temperature, ℃: ±0.5 (in the range from –10 to +85) ±1 (in the range from –30 to +100) ±2 (in the range from –55 to +125)
GTG-PT/M3 with a remote temperature sensor on a cable
GTG-PT/M3/PLANKA with a remote temperature sensor on a cable and additional mounting plates (option /PLANKA)
GTG-PT/M3/VD with built-in temperature sensor (option /VD)
GTG-PT/M3/VD with built-in temperature sensor (option /VD) and cable glands
GTG-PT2/M3 with a remote temperature sensor on a cable
GTG-PT2/M3/PLANKA with a remote temperature sensor on a cable and additional mounting plates (option /PLANKA)
GTG-PT2/M3/VD with built-in temperature sensor (option /VD)
GTG-PT2/M3/VD with a built-in temperature sensor (option /VD) and cable glands
Explosion-proof temperature sensor
Options
Options, accessories and versions
Marking
Increased switching current (X is the current value, A)
/X
Built-in sensor
/VD
The sensor housing is specially designed according to the customer's technical specifications
/KD
Mounting plate
/PLANK
Non-explosion-proof design
/PROM
Note:
- Ex-marking of GTG-PT…/VD: 1Ex db e ib IIC T6…T5 Gb. Ambient temperature range, °C: -55…+60.>
The GTG-PT/M3/VD and GTG-PT2/M3/VD thermostats with the /VD option are used to control external electrical devices and mechanisms based on ambient temperature. The main design feature of this option is the solid tip with a temperature sensor that does not contact surfaces other than the air.
220125, Republic of Belarus, Minsk, Shafarnyanskaya St., 11, room 89
Entrance
Please log in or register to continue
Code sent to .
Resend
Enter the email you used during registration. We'll send you a password recovery code.
Code sent to .
Create a new password for your account.
Create a new account
Code sent to .
Please fill in the details to complete your registration
You are registered
Your information has now been submitted for verification. Once verified, our manager will contact you to clarify the information. You can view the verification status in the "Profile" section
Contact us
Here you can ask any questions you may have, express your opinion on the quality of services or leave a suggestion
* Required fields
CAD " GORELTEX "
CAD "GoreltEx" 4.1.1.851 for Windows
EXE, 188 MB
The GORELTEX CAD system is designed to automatically generate drawings of explosion-proof terminal boxes, control stations, starters, and cable penetrations. The program is designed so that it does not require specialized skills in explosion-proof equipment design or in-depth knowledge of current standards, and the system's built-in algorithms eliminate errors in drawing creation.