GTG-KR-1M Explosion-Proof Single-Core Heating Cable with Mineral Insulation

Product Description

Designed for heating high-temperature pipelines, including those in explosive areas.

Scope: Hazardous areas of indoor and outdoor installations of classes 1 and 2 according to GOST IEC 60079-10-1-2013, hazardous areas of classes 21 and 22 according to GOST 31610.10-2-2017/IEC 60079-10-2.2015, normal.

Advantages

  • The cable has excellent mechanical strength and high corrosion resistance.

Frequently bought together

Markings

Explosion protection marking
1Ex 60079-30-1 IIC T3 Gb X*
Ex 60079-30-1 IIIC T200°C Db X*
1Ex 60079-30-1 IIC T1 Gb X*
Ex 60079-30-1 IIIC T400°C Db X*
1Ex 60079-30-1 IIC T1 Gb X*
Ex 60079-30-1 IIIC T450°C Db X*

*Only when used with GTG-N mounting kits
Degree of protection
IP67/IP68
Installation
Hazardous areas of indoor and outdoor installations of classes 1 and 2 according to GOST IEC 60079-10-1-2013, hazardous areas of classes 21 and 22 according to GOST 31610.10-2-2017/IEC 60079-10-2.2015

Technical data

Ambient temperature, °C
-60...+200 (nominal temperature for the GTG-KR-1M-200 cable);
-60...+400 (nominal temperature for the GTG-KR-1M-400 cable);
-60..+450* (nominal temperature for the GTG-KR-1M-450 cable);

*- The GTG-KR-1M-450 heating cable can heat up to +600°C, however, for explosion-hazardous areas these cables are designed for temperatures no higher than +450°C or are used with a temperature limiter
Minimum installation temperature, °C
-60
Maximum operating temperature, °C
+200/+400/+600
Temperature class
T1, T2, T3
Voltage, V
230/400 (up to 660)
Heat output, W/m
from 5 to 400
Cable sheath material
Copper, copper-nickel alloy or stainless steel
Climatic category
У1…5 (N1…5), NF1…5 (NF1…5), ХЛ1…3 (F1…3), ХЛ5 (F5)

Design parameters

Technical parameters for heating cables type GTG-KR-1M-200
Name Cross-section of the core, mm2 Nominal cable size, mm Minimum bending radius of cable at -20°C, mm Conductor resistance, Ohm/km
GTG-KR-1M-200-04S61 4,000 4,4 25 4,61
GTG-KR-1M-200-00004 4,300 5,9 4
GTG-KR-1M-200-07S41 2,500 3,8 7,41
GTG-KR-1M-200-00007 2,500 5,3 7
GTG-KR-1M-200-00012 1,500 3,4 12
GTG-KR-1M-200-00011 1,560 4,9 11
GTG-KR-1M-200-00018 1,000 3,1 18
GTG-KR-1M-200-00017 1,020 4,6 17
GTG-KR-1M-200-00025 0,693 3,7 25
GTG-KR-1M-200-00040 0,429 3,4 40
GTG-KR-1M-200-00063 0,273 3,2 63
Technical parameters for heating cables type GTG-KR-1M-400
Name Cross-section of the core, mm2 Nominal cable size, mm Minimum bending radius of cable at -20°C, mm Conductor resistance, Ohm/km
GTG-KR-1M-400-00011 1,560 4,9 7.5 cable diameters 11
GTG-KR-1M-400-00017 1,020 4,6 17
GTG-KR-1M-400-00025 0,693 3,7 25
GTG-KR-1M-400-00040 0,429 3,4 40
GTG-KR-1M-400-00063 0,273 3,2 63
GTG-KR-1M-400-00160 3,046 4,9 160
GTG-KR-1M-400-00250 1,960 4,4 250
GTG-KR-1M-400-00400 1,226 4 400
GTG-KR-1M-400-00630 0,769 3,7 630
GTG-KR-1M-400-01000 0,490 3,4 1000
GTG-KR-1M-400-01600 0,302 3,2 1600
Technical parameters for heating cables type GTG-KR-1M-450
Name Cross-section of the core, mm2 Nominal cable size, mm Minimum bending radius of cable at -20°C, mm Conductor resistance, Ohm/km
GTG-KR-1M-450-00160 6,747 6,5 7.5 cable diameters 160
GTG-KR-1M-450-00250 4,318 5,3 250
GTG-KR-1M-450-00400 2,699 4,7 400
GTG-KR-1M-450-00630 1,713 4,3 630
GTG-KR-1M-450-01000 1,080 3,9 1000
GTG-KR-1M-450-01600 0,675 3,6 1600
GTG-KR-1M-450-02500 0,432 3,4 2500
GTG-KR-1M-450-04000 0,270 3,2 4000
GTG-KR-1M-450-06300 0,171 3,2 6300
GTG-KR-1M-450-10000 0,108 3,2 10000

Changing any key parameters such as supply voltage or cable length will result in the output power differing from the design, which may require recalculation of the entire system and a change in the heating cable type.

Crossing heating cable strands with constant power is not permitted. The minimum permissible gap between heating cable strands is 20 mm.

Options

Options, accessories and versions
Marking
Cold lead length
/DVXXX
Length of heating part
/ДСХХХ
Marine version
/MORE
Non-explosion-proof design
/PROM

Additional information

Constant Power Cable Construction

Constant Power Cable Construction:

1. Heating core.

2. Mineral insulation.

3. Shell made of copper (GTG-KR-1M-200), copper-nickel alloy (GTG-KR-1M-400), stainless steel (GTG-KR-1M-450).

Submit request

Quantity
Additional description
0 / 300

Drag files here

CAD " GORELTEX ", questionnaires, necessary documents

Remaining: 20.00 MB
or
Model Breakdown
GTG-KR - 1X - 2X - 3X - 4X / 5X – TU 28.21.13-041-72453807-2017
1X - Number of cores: 1M - single-core with mineral insulation
2X - Maximum operating temperature of the cable
3X - Wire resistance
4X - Nominal voltage: 230, 400, 660
5X - Options, accessories and versions

Example: GTG-KR-1M-400-00011-230 - TU 28.21.13-041-72453807-2017.

Where to buy GORELTEX products

Saint Petersburg

Head office and production site

Telephone
Address
193149, Leningrad region, Vsevolozhsk district, Novosaratovka village, Rabochaya street, house 9, building 1
Read more

Moscow

Sales office

Telephone
Address
123112, Moscow, Presnenskaya Embankment, 6, building 2, business complex "Imperia Tower", floor 12, office No. 15
Read more

Kazan

Sales office

Telephone
Address
420061, Russia, Republic of Tatarstan, Kazan, st. Nikolay Ershova, 1A, Korston Business Center, floor 11, office No. 1110
Read more

Tyumen

Sales office and production site

Telephone
Address
625031, Russia, Tyumen, Shcherbakova St., 160G
Read more