[Ex ia Da] IIIС| Main parameters: | |||
| Inter-verification interval: | 2 years - BIG-3-1-22/AA* 4 years - BIG-3-1-22/AA/P* *By default, barriers are supplied without initial verification. Please indicate the need for verification when submitting your request. The verification cost will be specified when issuing the technical quotation. Verification increases the delivery time by approximately two weeks. |
||
| Operating temperature, °C: | -20 … +60 | ||
| Power supply, V: | 18..60 DC. Reverse polarity protection | ||
| Input signal: | K, E, S, B, J, T, R, N, …Pt100, Cu100, Cu50, BA1, BA2 | ||
| Line resistance (for RTD), Ohm: | ≤20 per line | ||
| Output signal, mA: | 4…20 | ||
| Load RL Source, Ohm: | ≤ 550 | ||
| Load RL Drain, Ohm: | < [(U‐3)/0.02] | ||
| Compensation accuracy, °C | 1 | ||
| Temperature compensation range, °C: | -20 … +60 | ||
| DIN rail mounting, mm: | 35 | ||
| Maximum safe voltage, V: | 250 | ||
| Intrinsic safety parameters: | |||
| terminals 1, 2, 3; 4, 5, 6 | |||
| II C: | II B: | II A : | |
| U0 , B: | 8,7 | 8,7 | 8,7 |
| I0 , mA | 33 | 33 | 33 |
| P0 , mW | 72 | 72 | 72 |
| C0 , μF | 5 | 35 | 700 |
| L0, mH | 28 | 84 | 224 |
| Transfer parameters: | |||
| Error, %: | 0,1 | ||
| Effect of temperature: | ≤30 x 10-6 /°C: | ||
| Response time, ms: | ≤ 500 | ||
| Power consumption, W: | ≤ 1,2 | ||
| Galvanic isolation, V: | |||
| Alternating current between intrinsically safe and non-intrinsically safe circuits |
≥ 3000 | ||
| Alternating current between the supply circuit and non-intrinsically safe circuits |
≥ 1500 | ||
| Insulation resistance (between input/output/power supply), MOhm: | ≥ 100 | ||
| type | Range, °C | Min. interval | Error |
| TO | ‐200… +1372 | < 300°C, ±0.3°C | ≥ 300°C, ±0.1% |
| E | ‐100…+1000 | < 300°C, ±0.3°C | ≥ 300°C, ±0.1% |
| J | ‐100… +1200 | < 300°C, ±0.3°C | ≥ 300°C, ±0.1% |
| N | ‐200… +1300 | < 300°C, ±0.3°C | ≥ 300°C, ±0.1% |
| S | ‐50… +1768 | < 500°C, ±0.5°C | ≥ 500°C, ±0.1% |
| R | ‐50… +1768 | < 500°C, ±0.5°C | ≥ 500°C, ±0.1% |
| T | ‐20… +400 | < 300°C, ±0.3°C | ≥ 300°C, ±0.1% |
| B | +400… +1820 | < 500°C, ±0.5°C | ≥ 500°C, ±0.1% |
| PT100 | ‐200°…+850 | < 100°C, ±0.1°C | ≥ 100°C, ±0.1% |
| Cu50 | ‐50… +150 | < 100°C, ±0.1°C | ≥ 100°C, ±0.1% |
| Cu100 | ‐50… +150 | < 100°C, ±0.1°C | ≥ 100°C, ±0.1% |

Connection diagram