BIG-3-1-22/AA Intrinsic Safety Barrier Temperature Input

Product Description

Conversion and transmission of thermocouple or resistance temperature sensor signals from hazardous areas into a current signal in a safe area. Requires an independent power source.
Setting up or changing the barrier parameters is performed using special software on a PC connected to the barrier via the BIG-NP adapter.

Advantages

  • Input, output and power supply signals are galvanically isolated from each other.
  • The electronic circuits of the barriers are coated with varnish, which additionally protects the elements from external factors.
  • High conversion accuracy ±0.1%
  • These products are designed with .
  • Mounting on a standard 35mm wide DIN rail.
  • Easy installation/dismantling of the product.
  • Availability of LED indication.
  • Has external cold junction compensation.
  • The barrier has a built-in self-diagnostic function.

Compliance with standards

GOST 31610.0-2014
GOST 31610.11-2014
GOST IEC 60079-14-2013
TR CU 012/2011
GOST IEC 61000-6-4-2016
GOST 30804.6.2-2013

Certificates

Markings

Explosion protection marking
[Ex ia Ga] IIC
[Ex ia Ga] IIB
[Ex ia Ga] IIA
[Ex ia Ma] I
[Ex ia Da] IIIС
Main parameters:
Inter-verification interval: 2 years - BIG-3-1-22/AA*
4 years - BIG-3-1-22/AA/P*

*By default, barriers are supplied without initial verification. Please indicate the need for verification when submitting your request. The verification cost will be specified when issuing the technical quotation. Verification increases the delivery time by approximately two weeks.

Operating temperature, °C: -20 … +60
Power supply, V: 18..60 DC. Reverse polarity protection
Input signal: K, E, S, B, J, T, R, N, …Pt100, Cu100, Cu50, BA1, BA2
Line resistance (for RTD), Ohm: ≤20 per line
Output signal, mA: 4…20
Load RL Source, Ohm: ≤ 550
Load RL Drain, Ohm: < [(U‐3)/0.02]
Compensation accuracy, °C 1
Temperature compensation range, °C: -20 … +60
DIN rail mounting, mm: 35
Maximum safe voltage, V: 250
Intrinsic safety parameters:
terminals 1, 2, 3; 4, 5, 6
II C: II B: II A :
U0 , B: 8,7 8,7 8,7
I0 , mA 33 33 33
P0 , mW 72 72 72
C0 , μF 5 35 700
L0, mH 28 84 224
Transfer parameters:
Error, %: 0,1
Effect of temperature: ≤30 x 10-6 /°C:
Response time, ms: ≤ 500
Power consumption, W: ≤ 1,2
Galvanic isolation, V:
Alternating current
between intrinsically safe and non-intrinsically safe circuits
≥ 3000
Alternating current
between the supply circuit and non-intrinsically safe circuits
≥ 1500
Insulation resistance (between input/output/power supply), MOhm: ≥ 100
Measurement limits and errors
type Range, °C Min. interval Error
TO ‐200… +1372 < 300°C, ±0.3°C ≥ 300°C, ±0.1%
E ‐100…+1000 < 300°C, ±0.3°C ≥ 300°C, ±0.1%
J ‐100… +1200 < 300°C, ±0.3°C ≥ 300°C, ±0.1%
N ‐200… +1300 < 300°C, ±0.3°C ≥ 300°C, ±0.1%
S ‐50… +1768 < 500°C, ±0.5°C ≥ 500°C, ±0.1%
R ‐50… +1768 < 500°C, ±0.5°C ≥ 500°C, ±0.1%
T ‐20… +400 < 300°C, ±0.3°C ≥ 300°C, ±0.1%
B +400… +1820 < 500°C, ±0.5°C ≥ 500°C, ±0.1%
PT100 ‐200°…+850 < 100°C, ±0.1°C ≥ 100°C, ±0.1%
Cu50 ‐50… +150 < 100°C, ±0.1°C ≥ 100°C, ±0.1%
Cu100 ‐50… +150 < 100°C, ±0.1°C ≥ 100°C, ±0.1%

Design parameters

Options

Options, accessories and versions
Marking
Marine version
/MORE

3D models

STP models
zip
Download

Configurator

BIGSmartGoreltech measuring device configurator for Windows
Download

Additional information

Connection diagram

Submit request

Quantity
Additional description
0 / 300

Drag files here

CAD " GORELTEX ", questionnaires, necessary documents

Remaining: 20.00 MB
or

Where to buy GORELTEX products

Saint Petersburg

Head office and production site

Telephone
Address
193149, Leningrad region, Vsevolozhsk district, Novosaratovka village, Rabochaya street, house 9, building 1
Read more

Moscow

Sales office

Telephone
Address
123112, Moscow, Presnenskaya Embankment, 6, building 2, business complex "Imperia Tower", floor 12, office No. 15
Read more

Kazan

Sales office

Telephone
Address
420061, Russia, Republic of Tatarstan, Kazan, st. Nikolay Ershova, 1A, Korston Business Center, floor 11, office No. 1110
Read more

Tyumen

Sales office and production site

Telephone
Address
625031, Russia, Tyumen, Shcherbakova St., 160G
Read more