The SHGV-UZGS are used for automatic monitoring of electrostatic grounding of sea and river vessels, tankers and barges during loading and unloading operations.
The device improves the safety of oil terminals by minimizing the risk of sparks, ignition of explosive atmospheres, and emergency situations, ensuring the protection of personnel, equipment, and infrastructure.
Automated measurements and signal transmission to the control station allow the device to be integrated into the terminal's security system. Specially designed cluminaires with a screw cluminaire ensure reliable electrical contact, resistant to vibration, wind, and mechanical impact.
1Ex db ia IIC T6 Gb X
1Ex db ia IIB+H2 T6 Gb
Ex ia tb IIIC T85°C Db
1Ex db ia IIC T5 Gb X
1Ex db ia IIB+H2 T5 Gb
Ex ia tb IIIC T95°C Db

| Design of the grounding element | Appearance | Cable |
| 2 |
standard pliers |
2x10 |
| 3 |
screw-type pliers |
2x16 |
| 4 | 2x35 | |
| 5 | 2x70 |
Note:
- The /UPS and /MODBUS options will be available soon.
- /ЩОРВ(А)ХХ is a mandatory option. For the basic ШГВ-УЗГС solution, the enclosure size is specified as /ЩОРВ464625. For other versions, the enclosure size must be specified during drawing preparation and order placement.
Operating algorithm of SHGV-UZGS grounding devices

The processes occurring during loading and unloading operations (loading flammable liquids, explosive bulk materials and gases) of road and railway tanks and reservoirs and during loading and unloading operations of ships are based on different physical phenomena.
Thus, during the loading and unloading of road and rail tankers and reservoirs, when two electrically neutral materials (for example, the tank and the liquid being filled) come into contact, an exchange of electrons occurs at the atomic level due to their different structures and the different strengths of the electron attraction forces. During the loading process, this exchange occurs at high speeds, and the electrons do not have time to return to their original positions.
Thus, the surface of one object develops an excess of electrons and a negative charge, while the surface of the other develops a deficit of electrons and a positive charge. The resulting difference in charges between the two objects results in a high potential difference, with the power being less than 1W.

A vessel in the water is constantly grounded, so no electrostatic charge develops. However, the risk of explosion remains due to another law of physics—the so-called "galvanic effect.

The ship's hull, the terminal's metal structures and the surrounding water (electrolyte) form a galvanic system in which a natural potential difference, known as the "galvanic effect", occurs between the various elements.
If a connection is established between these objects (for example, when a loading hose contacts a vessel's equipment), a closed electrical circuit with a high potential difference is created, with power levels reaching up to 500 watts. This affects inductive elements such as loading hoses or flexible hoses. When these connections are disconnected (the circuit is broken), the accumulated energy can cause a spark, which can ignite explosive vapors.
IMPORTANT! Potential differences begin to build up during vessel mooring, not just during loading. Additional factors, such as corrosion protection systems, railway tracks near the terminal, and other infrastructure, can increase this potential difference, creating potentially hazardous electrical conditions.
To prevent the risk of explosion, it is necessary to establish a safe equipotential low-impedance connection with a resistance below 100 ohms between the vessel and the berth and to continuously monitor this connection.
Any attempt to use conventional grounding devices to ground a vessel will result in an immediate breakdown. Their use for grounding vessels is STRICTLY PROHIBITED!
A special device, the SHGV-UZGS, was developed for grounding sea and river vessels, tankers and barges.
This device has no analogues among Russian manufacturers and has a number of significant design differences from conventional grounding devices.