DVG-TERMOSTAT1 Explosion-Proof Bimetal Thermostats

Product Description

DVG-TERMOSTAT1 Bimetal Thermostats are designed to collect information and control the external temperature of heating systems, and regulate the internal temperature of heated instrument cabinets at explosive facilities.

Advantages

  • Suitable for controlling both heating and cooling systems;
  • Possibility of manufacturing based on housings of other sizes;
  • Controls loads up to 10A directly;
  • Switching on higher values ​​or 3-phase circuits is accomplished through a contactor;
  • Possibility of installing up to 3 cable glands.

Frequently bought together

Compliance with standards

TR CU 012/2011
TR CU 004/2011
GOST R IEC 60079-0-2011
GOST 14254-96 (IEC 529-89)
Chapter 7.3 of the Electrical Installation Code
Chapter 7.4 of the Electrical Installation Code
GOST 30852.0-2002 (IEC 60079-0:1998)
GOST 30852.8-2002 (IEC 60079-0:1998)
GOST IEC 61241-1-1-2011
GOST 30852.1-2002 (IEC 60079-1:1998)
GOST R IEC 60079-31-2010
GOST 30852.10-2002 (IEC 60079-11:1999)

Certificates

Markings

Explosion protection marking
1Ex db IIC T6...T5 Gb
1Ex ia IIC T6...T5 Gb
0Ex ia IIC T6...T5 Ga Х
Ex tb IIIC T85°С...T100°С Db
Ex ia IIIC T85°С...T100°С Da
Marking of mining equipment
RN1/RN2
Degree of protection
IP66/IP67
Installation
Category II for gas subgroups IIA, IIB, IIC, zones 1, 2;
Category III for dust, explosive dust atmospheres, volatile particles, non-conductive and conductive dust;
Underground workings that are not hazardous for gas (methane) and coal dust;
Non-hazardous zone of surface structures and open areas

Technical data

Ambient temperature, °C
-60...+85 (T5/T100°C)
-60...+60 (T6/T85°C)
Electrical characteristics
Un= ~380 V, In=4 A, f=50 Hz
Un= ~220 V, In=10 A, f 50 Hz
Un= 30 V, In=10 A
Grounding
2 ground cluminaires (internal and external) made of stainless steel
Cover fastening
Threaded connection
Coating
Polymer-epoxy paint with antistatic properties, friction-proof, spark-proof, resistant to working environments and ionizing radiation. Color RAL 7035
Material
Aluminum alloy with alloying modifiers
Housing fastening
2 external mounting points
Protection class against electric shock
I
Weight, kg
1,5
Climatic category
NF1 (as required NF2, NF3, NF4, NF5, HL1, HL2, HL3, HL5, T1, T2, T3, T5, MU1, MU2, MU3, MU4, W2.1 , W5 )

Design parameters

Explosion-proof junction boxes for energy distribution and data collection DVG-TERMOSTAT1 (S-TERMOSTAT)

Response graph using the example of DVG-TERMOSTAT1-(21/17)0

Response graph using the example of DVG-TERMOSTAT1-(21/17)0

Thermostat type Contact type Response ranges
DVG-THERMOSTAT1-(60/78)1 1NZ 60-68°C...72-78°C
DVG-THERMOSTAT1-(0/18)1 1NZ 0-8°C...12-18°C
DVG-THERMOSTAT1-(-5/13)1 1NZ -5-3°C...7-13°C
DVG-THERMOSTAT1-(21/17)0 1NO 21-29°C...11-17°C
DVG-THERMOSTAT1-(2/-2)0 1NO 2-8°C...-10- -2°C
DVG-THERMOSTAT1-(66/62)0 1NO 66-74°C...56-62°C

Options

Options, accessories and versions
Marking
Degree of protection against external influences IP67
/IP67
Painting the outer surface in the color according to the customer's requirements
/RAL (code)
Marine version
/MORE
Non-explosion-proof design
/PROM
River execution
/RIVER
Mining normal design
/RN
Mounting bracket
/BRACKET
Stainless steel lid chain
/CHAIN
Option Correspondence Table
PROM SEA RIVER RN BRACKET CHAIN RAL (code)
PROM + + + + + +
SEA + + - + + +
RIVER + + - + + +
RN + - - + + +
BRACKET + + + + + +
CHAIN + + + + + +
RAL (code) + + + + + +

Additional information

Submit request

Configurator
Operating range, °C:
Quantity
Additional description
0 / 300

Drag files here

CAD " GORELTEX ", questionnaires, necessary documents

Remaining: 20.00 MB
or
Model Breakdown
1X ( 2X ) - 3X / 4X – TU 27.12.31-037-72453807-2017
1X - Thermostat type
2X - Number and cross-section of terminals
3X - Number of cable glands (max. 3 pcs) and side of location
4X - Options, accessories and versions

Example: DVG-THERMOSTAT1-(2/-2)0 (4RN2) - KNV2N(A) -TU 27.12.31-037-72453807-2017

where ДВГ-ТЕРМОСТАТ1-(2/-2)0 is the thermostat type,
4RN2 is the number of terminals and their cross-section,
КНВ2Н(A) is the number, type and side of the cable entry.

Where to buy GORELTEX products

Saint Petersburg

Head office and production site

Telephone
Address
193149, Leningrad region, Vsevolozhsk district, Novosaratovka village, Rabochaya street, house 9, building 1
Read more

Moscow

Sales office

Telephone
Address
123112, Moscow, Presnenskaya Embankment, 6, building 2, business complex "Imperia Tower", floor 12, office No. 15
Read more

Kazan

Sales office

Telephone
Address
420061, Russia, Republic of Tatarstan, Kazan, st. Nikolay Ershova, 1A, Korston Business Center, floor 11, office No. 1110
Read more

Tyumen

Sales office and production site

Telephone
Address
625031, Russia, Tyumen, Shcherbakova St., 160G
Read more