Explosion-proof self-regulating cable GTG-KSN up to +85 °C

Product Description

The GTG-KSN self-regulating low-temperature parallel heating cable is used to protect against freezing and maintain process temperatures up to +65°C for pipelines, tanks, automation facilities, and any other objects that require additional freeze protection.

For organic corrosive environments, it is recommended to use cables with a fluoropolymer sheath.

For weak inorganic media, it is recommended to use cables with a polyolefin sheath.

Scope: Hazardous areas of indoor and outdoor installations of classes 1 and 2 according to GOST IEC 60079-10-1-2013, hazardous areas of classes 21 and 22 according to GOST 31610.10-2-2017/IEC 60079-10-2.2015, normal.

Advantages

  • Saving electricity.
  • Easy installation and operation.
  • No overheating effect.

Frequently bought together

Compliance with standards

TR CU 012/2011
TR CU 004/2011
TR CU 037/2016

Certificates

Markings

Explosion protection marking
1Ex 60079-30-1 IIC T6 Gb X*
Ex 60079-30-1 IIIC T85°C Db X*

*Only when used with GTG-N mounting kits
Degree of protection
IP66/IP67/IP68
Installation
Category II for gas subgroups IIA, IIB, IIC, zones 1, 2;
Category III for dust, explosive dust atmospheres containing volatile particles, non-conductive and conductive dust;
Non-hazardous zone of surface structures and open areas

Technical data

Ambient temperature, °C
-60...+85 (maximum permissible temperature without load)
Minimum installation temperature, °C
P/F: -40/-60
Maximum supported temperature, °C
+65
Maximum permissible temperature without load (1000 hours in total), °C
+85
Temperature class
T6
Voltage, V
~220-240
Nominal power, W/m
10, 15, 25, 33
Cable sheath material
Fluoropolymer, polyolefin
Climatic category
У1…5 (N1…5), NF1…5 (NF1…5), ХЛ1…3 (F1…3), ХЛ5 (F5)

Design parameters

Technical parameters of heating cables type GTG-KSN
Name Nominal power
(W/m at 10°C)
Thickness, mm Width, mm Weight, kg/km
GTG-KSN-10P 10 6,1±0,3 12,4±0,6 117±10%
GTG-KSN-15P 15
GTG-KSN-25P 25
GTG-KSN-33P 33
GTG-KSN-10F 10 5,7±0,3 12,0±0,6 119±10%
GTG-KSN-15F 15
GTG-KSN-25F 25
GTG-KSN-33F 33
Maximum length of cable circuit when using type C circuit breaker, m
Type Switch-on temperature, °C Maximum length of
heating cable circuit, m
16A 20A 32A
GTG-KSN-10P(F) 10 152 180 180
0 133 167 180
-20 106 133 180
GTG-KSN-15P(F) 10 137 162 162
0 121 151 162
-20 96 120 162
GTG-KSN-25P(F) 10 107 126 126
0 95 119 126
-20 77 96 126
GTG-KSN-33P(F) 10 84 104 108
0 75 93 108
-20 61 76 108

The given figures are intended only for preliminary estimation of the length of electric heating circuits.

For an accurate calculation, please contact ZAVOD GORELTEX CO. LTD.. To ensure safety and fire protection, a 30 mA RCD must be used.

If the design results in a higher earth leakage current, for devices with adjustable tripping current, the preferred tripping current level is 30 mA above the heating cable manufacturer's specified earth leakage current rating or the next available tripping current value for devices with non-adjustable tripping current, up to a maximum of 300 mA.

Options

Options, accessories and versions
Marking
Marine version
/MORE
Non-explosion-proof design
/PROM

Additional information

Graph of the dependence of power on temperature of low-temperature self-regulating heating cables GTG-KSN

A - GTG-KSN-33

B - GTG-KSN-25

C - GTG-KSN-15

D - GTG-KSN-10

Self-regulating cable device

Self-regulating cable device:

1. Current-carrying conductors made of copper.

2. Semiconductor self-regulating matrix.

3. Fluoropolymer insulation.

4. Braiding of tinned copper wires.

5. Shell made of fluoropolymer (F) or polyethylene (P).

Mounting kits:

Submit request

Quantity
Additional description
0 / 300

Drag files here

CAD " GORELTEX ", questionnaires, necessary documents

Remaining: 20.00 MB
or
Model Breakdown
GTG-KSN - 1X 2X / 3X – TU 28.21.13-041-72453807-2017
1X - Linear power: 10 - 10 W/m, 15 - 15 W/m, 25 - 25 W/m, 33 - 33 W/m
2X - Insulation material: F - fluoropolymer, P - polyolefin
3X - Options, accessories and versions

Example: GTG-KSN-10F-TU 28.21.13-041-72453807-2017.

Where to buy GORELTEX products

Saint Petersburg

Head office and production site

Telephone
Address
193149, Leningrad region, Vsevolozhsk district, Novosaratovka village, Rabochaya street, house 9, building 1
Read more

Moscow

Sales office

Telephone
Address
123112, Moscow, Presnenskaya Embankment, 6, building 2, business complex "Imperia Tower", floor 12, office No. 15
Read more

Kazan

Sales office

Telephone
Address
420061, Russia, Republic of Tatarstan, Kazan, st. Nikolay Ershova, 1A, Korston Business Center, floor 11, office No. 1110
Read more

Tyumen

Sales office and production site

Telephone
Address
625031, Russia, Tyumen, Shcherbakova St., 160G
Read more