Saint Petersburg
Head office and production site
TU 28.21.13-041-72453807-2017
1Ex 60079-30-1 IIC T5 Gb X
Ex 60079-30-1 IIC T95°C Db X
1Ex 60079-30-1 IIC T4 Gb X
Ex 60079-30-1 IIC T125°C Db X
1Ex 60079-30-1 IIC T3 Gb X
Ex 60079-30-1 IIC T155°C Db X
1Ex 60079-30-1 IIC T3 Gb X
Ex 60079-30-1 IIC T185°C Db X| Name | GTG-KABEL3-90-15 | GTG-KABEL3-120-30 | GTG-KABEL3-150-40 | GTG-KABEL3-180-60 |
| Power, W/m | 15±10% | 30±10% | 40±10% | 60±10% |
| Maximum supported temperature, °C | +(90±5) | +(120±10) | +(150±10) | +(180±10) |
| Maximum allowable temperature without load (1000 hours in total) | +205 | +205 | +205 | +205 |
| Nominal cable size, mm | 6.4x11.4 | 6.4x11.4 | 6.4x11.4 | 6.4x11.4 |
| Maximum length of the heating section at an ambient temperature of -20°C, m | 1 | 1 | 1 | 1 |
| Temperature class | T5/T95°C | T4/T125°C | T3/T155°C | T3/T185°C |
| Cable sheath material | teflon - fluoropolymer | teflon - fluoropolymer | teflon - fluoropolymer | teflon - fluoropolymer |
| Minimum installation temperature, °C | -60 | -60 | -60 | -60 |
| Dimensions of the electrical protective installation | Switch-on temperature, °C | Maximum length of heating cable per circuit (m) at 400V AC | |||
| GTG-KABEL3-90-15 | GTG-KABEL3-120-30 | GTG-KABEL3-150-40 | GTG-KABEL3-180-60 | ||
| 16A | (-20°C) | 700 | 320 | 240 | 150 |
| (+10°C) | 700 | 320 | 240 | 150 | |
| 25A | (-20°C) | 1100 | 525 | 390 | 250 |
| (+10°C) | 1100 | 525 | 390 | 250 | |
| 32A | (-20°C) | 1400 | 681 | 500 | 320 |
| (+10°C) | 1400 | 681 | 500 | 320 | |
| 40A | (-20°C) | 1780 | 858 | 630 | 410 |
| (+10°C) | 1780 | 858 | 630 | 410 | |

Graph of the dependence of linear power on temperature
for constant power heating cables of the GTG-KABEL3 type.






Drag files here
CAD " GORELTEX ", questionnaires, necessary documents
Example: GTG-KABEL3-120-30-30-TU 28.21.13-041-72453807-2017
Head office and production site
Sales office
Sales office
Sales office and production site
Sales office
Sales office