1Ex db IIC T6...T5 Gb
0Ex ia IIC T6...T5 Ga X
Ex tb IIIC T70°С Db
Open circuit connection diagram (serial connection)
Short circuit connection diagram (parallel connection)
| Type of control panel | Parallel connection (for short circuit) | Sequential connection (on opening) |
| LB-07 | Rд must provide current consumption >15 mA, Rок = 2 kOhm, VDок = KD522 | Rd = 11 kOhm, Rok = 2 kOhm, VDok = KD522 |
| Beam | Rd = 2.4 kOhm, Rok = 2.4 kOhm, VDok = KD521A | Rd = 2.2 kOhm, Rok = 2.4 kOhm, VDok = KD521A |
| PPK-2 | Rd = 1.2 kOhm, Rok = 3.6 kOhm, VDok = KD521A | Rd = 10.0 kOhm, Rok = 3.6 kOhm, VDok = KD521A |
| Bolide | Rд = 1.5 kOhm, Rок = 4.7 kOhm, VДок do not install | Rд = 8.2 kOhm, Rок = 4.7 kOhm, VДок do not install |
| Yakhont-16i | Rд = 1.8 kOhm, Rок = 8.2 kOhm, VДок do not install | Not applicable |
| VERS | Rд = 820 Ohm, Rок = 7.5 kOhm, VДок do not install | Rд = 10 kOhm, Rок = 7.5 kOhm. Do not install VДок |
Differences between class A IPR and class B IPR in accordance with GOST R 53325-2012: class A IPR (IP-535- GORELTEX 1-A, IP-535- GORELTEX 2-A) are activated after the displacement of the indestructible drive element, accompanied by a change in the appearance of the IPR.
Class B IPR (IP-535-GORELTEX1-B) are activated after two actions have been performed:
1. providing access to the drive element by destroying or displacing the protective element designed as a class A drive element;
2. subsequent manual activation of the drive element.