Saint Petersburg
Head office and production site
Telephone
Address
193149, Leningrad region, Vsevolozhsk district, Novosaratovka village, Rabochaya street, house 9, building 1
[Ex ia Ga] IIC
[Ex ia Ga] IIB
[Ex ia Ga] IIA
[Ex ia Ma] I
[Ex ia Da] IIIС| Main parameters | |||
| Response time | ≤ 1 s | ||
| Power consumption | 1 W (24 V, single output) | ||
| Dielectric strength |
alternating current (intrinsically safe and non-intrinsically safe sides) | ≥ 2500 V | |
| AC (power/non-intrinsically safe side) | ≥ 500 V | ||
| Insulation resistance (input/output) |
≥ 100 MOhm | ||
| Operating temperature | -20°C… +60°C | ||
| Storage temperature | -40°C… +80°C | ||
| Dimensions | width | 15.8 mm | |
| height | 121.6 mm | ||
| depth | 104.8 mm | ||
| Transfer parameters | |||
| Compensation error | 1°C (compensation temperature range: -20°C ~ +60°C) | ||
| Limits of permissible additional error due to temperature changes |
0.01%/ºС (the normalizing value for the given error is the input signal range) | ||
| Maximum safe voltage | 250 V | ||
| Intrinsic safety parameters | terminals 1, 2, 3 | ||
| II C : | II B, IIIC: | II A, I : | |
| U0, B | 7,3 | 7,3 | 7,3 |
| I0, mA | 27 | 27 | 27 |
| P0, mW | 50 | 50 | 50 |
| C0, μF | 12 | 151 | 700 |
| L0, mH | 28 | 84 | 224 |
| Nutrition | |||
| Power supply | =18-32 Reverse polarity protection | ||
| Input parameters | |||
| Input signal | Type K, E, S, B, J, T, R, N, Pt100, Cu50, Cu100 | ||
| Input resistance | ≤20 Ohm/line (RTD) | ||
| Output parameters | |||
| Output signal | 4-20 mA | ||
| Regardless of the input signal fault condition (except for an open or short circuit, when the output is 0 mA), the output signal matches the input signal within the measurement range. The maximum value will not exceed 110% of the upper limit of the measurement range. For example, with a 0-20 mA output signal, the minimum value can be 0 mA, and the maximum output value will not exceed 22 mA. |
|||
| Load resistance RL | ≤500 Ohm | ||
| Measurement limits and errors | |||
| Type | Range, °C | The main error | |
| Pt100 | -200 ~ +850 | <150°C, ±0.15°C | ≥150°C, ±0.1%1) |
| Cu50 | -50 ~ +150 | <150°C, ±0.15°C | ≥150°C, ±0.1%1) |
| Cu100 | -50 ~ +150 | <150°C, ±0.15°C | ≥150°C, ±0.1%1) |
| THA (K) | -200 ~ +1372 | <500°C, ±0.5°C | ≥500°C, ±0.1%1),2) |
| THKn (E) | -100 ~ +1000 | <500°C, ±0.5°C | ≥500°C, ±0.1%1),2) |
| TFA (J) | -100 ~ +1200 | <500°C, ±0.5°C | ≥500°C, ±0.1%1),2) |
| TNN (N) | -200 ~ +1300 | <500°C, ±0.5°C | ≥500°C, ±0.1%1),2) |
| TPP (S) | -50 ~ +1768 | <800°C, ±0.8°C | ≥800°C, ±0.1%1),2) |
| Chamber of Commerce and Industry (R) | -50 ~ +1768 | <800°C, ±0.8°C | ≥800°C, ±0.1%1),2) |
| TMK (T) | -20 ~ +400 | <500°C, ±0.5°C | ≥500°C, ±0.1%1),2) |
| TPR (B) | +400 ~ +1820 | <800°C, ±0.8°C | ≥800°C, ±0.1%1),2) |
| 1) the normalizing value for the given error is the range of the input signal 2) without taking into account the error in measuring the cold junction temperature |
|||


Drag files here
CAD " GORELTEX ", questionnaires, necessary documents
Head office and production site
Sales office
Sales office
Sales office and production site
Sales office
Sales office