BIG-K-6-1/12 Intrinsic Safety Barrier Potentiometer Signal

Product Description

The intrinsic safety barrier converts three-wire potentiometer signals from the hazardous area into current signals for the safe area.

Setting up or changing the barrier parameters is performed using a hand-held programmer or special software on a PC.

Advantages

  • Input, output and power supply signals are galvanically isolated from each other.
  • The electronic circuits of the barriers are coated with varnish, which additionally protects the elements from external factors.
  • Mounting on the BIG-BAZA or MTL4500 backplane.
  • Speed ​​and ease of installation.
  • Availability of LED indication.

Compliance with standards

GOST 31610.0-2014
GOST 31610.11-2014
GOST IEC 60079-14-2013
TR CU 012/2011
GOST IEC 61000-6-4-2016
GOST 30804.6.2-2013

Certificates

Markings

Explosion protection marking
[Ex ia Ga] IIC
[Ex ia Ga] IIB
[Ex ia Ga] IIA
[Ex ia Ma] I
[Ex ia Da] IIIС
Main parameters
Response time ≤ 1 s
Power consumption 1.5 W (24 V, two outputs)
Dielectric
strength
alternating current (intrinsically safe and non-intrinsically safe sides) ≥ 2500 V
AC (power/non-intrinsically safe side) ≥ 500 V
Insulation resistance
(input/output)
≥ 100 MOhm
Operating temperature -20°C… +60°C
Storage temperature -40°C… +80°C
Dimensions width 15.8 mm
height 121.6 mm
depth 104.8 mm
Transfer parameters
Compensation error 0.1% (the normalizing value for the given error is the input signal range)
Limits of permissible additional error
due to temperature changes
0.01%/ºС (the normalizing value for the given error is the input signal range)
Maximum safe voltage 250 V
Intrinsic safety parameters terminals 1, 2, 3
II C : II B, IIIC: II A, I :
U0, B 7,3 7,3 7,3
I0, mA 27 27 27
P0, mW 50 50 50
C0, μF 12 151 700
L0, mH 28 84 224
Nutrition
Power supply =18-32 Reverse polarity protection
Input parameters
Input signal 3-wire potentiometer 0-10 kOhm
Output parameters
Output signal 4-20 mA
Regardless of the input signal fault condition (except for an open or short circuit, when the output is 0 mA), the output signal matches the input signal within the measurement range.
The maximum value will not exceed 110% of the upper limit of the measurement range.
For example, with a 0-20 mA output signal, the minimum value can be 0 mA, and the maximum output value will not exceed 22 mA.
Load resistance RL ≤500 Ohm

Design parameters

Connection diagram
Overall dimensions

Options

Options, accessories and versions
Marking
Marine version
/MORE

Additional information

Submit request

Quantity
Additional description
0 / 300

Drag files here

CAD " GORELTEX ", questionnaires, necessary documents

Remaining: 20.00 MB
or

Where to buy GORELTEX products

Saint Petersburg

Head office and production site

Telephone
Address
193149, Leningrad region, Vsevolozhsk district, Novosaratovka village, Rabochaya street, house 9, building 1
Read more

Moscow

Sales office

Telephone
Address
123112, Moscow, Presnenskaya Embankment, 6, building 2, business complex "Imperia Tower", floor 12, office No. 15
Read more

Kazan

Sales office

Telephone
Address
420061, Russia, Republic of Tatarstan, Kazan, st. Nikolay Ershova, 1A, Korston Business Center, floor 11, office No. 1110
Read more

Tyumen

Sales office and production site

Telephone
Address
625031, Russia, Tyumen, Shcherbakova St., 160G
Read more