BIG-2-2-22 Intrinsic Safety Barrier Discrete Output

Product Description

The barrier is designed for the intrinsically safe transmission of discrete signals (dry contact) from a non-hazardous area to an explosive area and for controlling devices such as electromagnetic valves, audible signaling devices, etc.

Advantages

  • Input, output and power supply signals are galvanically isolated from each other.
  • The electronic circuits of the barriers are coated with varnish, which additionally protects the elements from external factors.
  • High conversion accuracy ±0.1%
  • Mounting on a standard 35mm wide DIN rail.
  • Easy installation/dismantling of the product.
  • The compact body allows for tighter installation.
  • Availability of LED indication.

Compliance with standards

GOST 31610.0-2014
GOST 31610.11-2014
GOST IEC 60079-14-2013
TR CU 012/2011
GOST IEC 61000-6-4-2016
GOST 30804.6.2-2013

Certificates

Markings

Explosion protection marking
[Ex ia Ga] IIC
[Ex ia Ga] IIB
[Ex ia Ga] IIA
[Ex ia Ma] I
[Ex ia Da] IIIС
Main parameters:
Operating temperature, °C: -20 … +60
Power supply, V: = 18..60 Reverse polarity protection
Input signal: Dry contact
Output signal current value, mA: ≤ 45
Output voltage, V: > 11.25 DC
Open circuit voltage, V: 21.5 DC
DIN rail mounting, mm: 35
Maximum safe voltage, V: 250
Intrinsic safety parameters:
terminals 1, 2; 3,4
II C: II B: II A :
U0 , B: 25,2 25,2 25,2
I0 , mA 117 117 117
P0 , mW 738 738 738
C0 , μF 0,107 0,82 2,9
L0, mH 1,5 4,5 12
Transfer parameters:
Response time, ms: ≤ 20
Power consumption, W: ≤ 1,4
Galvanic isolation, V:
alternating current
between intrinsically safe and non-intrinsically safe circuits
≥ 3000
alternating current
between the supply circuit and non-intrinsically safe circuits
≥ 1500
Insulation resistance (between input/output/power supply), MOhm: ≥ 100
Output signal value in safe state, mA: <3.6 or >21.5

Design parameters

Connection diagram
Overall dimensions

Options

Options, accessories and versions
Marking
Marine version
/MORE

3D models

STP models
zip
Download

Additional information

Submit request

Quantity
Additional description
0 / 300

Drag files here

CAD " GORELTEX ", questionnaires, necessary documents

Remaining: 20.00 MB
or

Where to buy GORELTEX products

Saint Petersburg

Head office and production site

Telephone
Address
193149, Leningrad region, Vsevolozhsk district, Novosaratovka village, Rabochaya street, house 9, building 1
Read more

Moscow

Sales office

Telephone
Address
123112, Moscow, Presnenskaya Embankment, 6, building 2, business complex "Imperia Tower", floor 12, office No. 15
Read more

Kazan

Sales office

Telephone
Address
420061, Russia, Republic of Tatarstan, Kazan, st. Nikolay Ershova, 1A, Korston Business Center, floor 11, office No. 1110
Read more

Tyumen

Sales office and production site

Telephone
Address
625031, Russia, Tyumen, Shcherbakova St., 160G
Read more