Saint Petersburg
Head office and production site
Telephone
Address
193149, Leningrad region, Vsevolozhsk district, Novosaratovka village, Rabochaya street, house 9, building 1
[Ex ia Ga] IIC
[Ex ia Ga] IIB
[Ex ia Ga] IIA
[Ex ia Ma] I
[Ex ia Da] IIIС| Main parameters: | |||
| Operating temperature, °C: | -20 … +60 | ||
| Power supply, V: | = 18..60 Reverse polarity protection | ||
| Input signal: | Dry. contact open collector | ||
| Output signal current value, mA: | ≤ 45 | ||
| Output voltage, V: | > 11.25 DC | ||
| Open circuit voltage, V: | 21.5 DC | ||
| DIN rail mounting, mm: | 35 | ||
| Maximum safe voltage, V: | 250 | ||
| Intrinsic safety parameters: | |||
| terminals 1, 2; 3,4 | |||
| II C: | II B: | II A : | |
| U0 , B: | 25,2 | 25,2 | 25,2 |
| I0 , mA | 117 | 117 | 117 |
| P0 , mW | 738 | 738 | 738 |
| C0 , μF | 0,107 | 0,82 | 2,9 |
| L0, mH | 1,5 | 4,5 | 12 |
| Transfer parameters: | |||
| Response time, ms: | ≤ 20 | ||
| Power consumption, W: | ≤ 1,4 | ||
| Galvanic isolation, V: | |||
| alternating current between intrinsically safe and non-intrinsically safe circuits |
≥ 3000 | ||
| alternating current between the supply circuit and non-intrinsically safe circuits |
≥ 1500 | ||
| Insulation resistance (between input/output/power supply), MOhm: | ≥ 100 | ||
| Output signal value in safe state, mA: | <3.6 or >21.5 | ||


Drag files here
CAD " GORELTEX ", questionnaires, necessary documents
Head office and production site
Sales office
Sales office
Sales office and production site
Sales office
Sales office