[Ex ia Ga] IIC
[Ex ia Ga] IIB
[Ex ia Ga] IIA
[Ex ia Ma] I
[Ex ia Da] IIIС| Main parameters: | |||
| Safety Integrity Level (SIL): | SIL 2 | ||
| Operating temperature, °C: | -20 … +60 | ||
| Power supply, V: | = 20..30 Reverse polarity protection | ||
| Input signal: | Dry contact/NAMUR | ||
| Output signal: | Relay output | ||
| Response parameters: | |||
| In. signal > 2.1 mA “1” | Yellow, constant glow | ||
| In. signal < 1.2 mA “0” | Yellow, off | ||
| Open Circuit Voltage, V: | 9,2 | ||
| Short-circuit current, mA: | 9 | ||
| Permissible load at 2A, V: | ~250 or =30 | ||
| DIN rail mounting, mm: | 35 | ||
| Maximum safe voltage, V: | 250 | ||
| Intrinsic safety parameters: | |||
| terminals 1, 2 | |||
| II C: | II B: | II A : | |
| U0 , B: | 10,5 | 10,5 | 10,5 |
| I0 , mA | 11,3 | 11,3 | 11,3 |
| P0 , mW | 29,7 | 29,7 | 29,7 |
| C0 , μF | 0,644 | 11 | 52 |
| L0, mH | 35,255 | 105 | 282 |
| Transfer parameters: | |||
| Response time, ms: | ≤ 20 | ||
| Power consumption, W: | 1 | ||
| Relay resource in thousands of cycles: | 100 | ||
| Response frequency, Hz: | < 10 | ||
| Galvanic isolation, V: | |||
| AC | ≥ 3000 | ||
| alternating current between intrinsically safe and non-intrinsically safe circuits |
≥ 1500 | ||
| Insulation resistance (between input/output/power supply), MOhm: | ≥ 100 | ||
| Output signal value in safe state, mA: | <3.6 or >21.5 | ||


| DIP switches | position | |
| switch | a | b |
| S1 | Normal output mode 1 | Inverted output mode 1 |
| S2 | Fault indication on | Failure indication off |
| S3 | Normal output mode 2 | Inverted output mode 2 |
LED indication algorithm.
If the input current is less than 0.08 mA, an open circuit condition is detected on the input line, the device enters a safe functional state, and the output relay is de-energized. If the input current is greater than 6 mA, an input line short circuit condition is detected, the device enters a safe functional state, the output relay is de-energized, and the indicator flashes red.