| Main parameters | |
| Power supply type | from the contour |
| Voltage, V DC | 20…32 |
| Heat output, W | ≤ 2.2 at =24 V |
| Current consumption at =24V, mA | ≤ 90 |
| Test pulse duration, ms, no more than | 3 |
| Cable resistance, Ohm | 15 |
| Input devices | safety switch, discrete output signal |
| Signal type | 2no + 2nz |
| Contact type | forced management |
| Contact material | AgSnO2 + 0.2 μm Au |
| Load characteristics | AC-15: 5 A / 230 V, DC-13: 5 A / 24 V |
| Fuse characteristics | 10A gL/gG(no), 6A gL/gG(no) |
| Switching on, ms, no more than | 200 |
| Opening, ms, no more than | 50 |
| Switching frequency, Hz, no more than | 4 |
| Electromagnetic compatibility | IEC/EN 80947, IEC 61326-3-1, IEC/EN 61000-6-2, IEC/EN 61000-6-4 |
| Nominal insulation voltage , V AC |
250 |
| Nominal pulse voltage, V | 6000 (1.2/50 µs) |
| Dielectric strength, V | 1500 (within 1 min) |
| Gaps and leaks | According to IEC 80947-1 |
| Vibration, Hz | 10…55 (0.35 mm) |
| Overvoltage category | III |
| Degree of pollution | 2 |
| Degree of dust and moisture protection | IP20 |
| Operating temperature, °C | -20…. +60 |
| Storage temperature, °C | -40…. +80 |
| Altitude above sea level, m | ≤ 2000 |
| Number of operations, cycles | 10 x 106 |
| Security parameters | |
| Safety Integrity Level (SIL) | 3 |
| Average diagnostic coverage (DC avg), % | 99 |
| Mean time to failure (MTTFD), years | 164 |
| Hardware Fault Tolerance (HFT) | 1 |
| Safe failure rate (SFF), not less than, % | 99 |
| Average probability of dangerous failure on demand (PFDavg/PTI) | 1,53×10-5 |
| Probability of failure per hour (PFH), 1/h | 1,77×10-10 |
| Stop category | 0 |
| Connection diagram | |
![]() |
|

1-channel, FSC* connection.
System loop detection.
Feedback loop.
Use in high-request mode.
* Fail Safe Controller (FSC) is an electronic device that monitors the system and ensures its safe and reliable operation even in the event of a failure.
FSCs are used in industrial settings to protect equipment from failure, damage, or destruction due to unexpected conditions. The device continuously monitors system operation and takes immediate action upon detecting potential problems before they become dangerous or damaging.